SV250000 – Arc Killer SV-25 Mechanism A

SV-25 Arc Killer
for use in medium voltage incoming cubicle or cable field type DF-A

Offers an additional protection against negative effects from an internal arc.
– extinguishes the arc in less then 50 ms
– for use in air insulated switchgear
– patented design

Includes:
– earthing knife on support for mounting on DF-A side panel
– drive mechanism

IEC tested at KEMA according IEC 60298 Annex AA.

Test cycle:
1. rated power frequency withstand voltage 1 min: 38 kV
2. rated lightning impulse withstand voltage: 95 kV (15x + en 15x -)
3. internal arc withstand test 14/16/20 kA 1 s: alle 6 criteria voldaan
4. rated power frequency withstand voltage 1 min: 50 kV

SV250001 -Arc Killer SV-25 on VA(S)-2

SV-25 Arc Killer
for mounting on vacuum circuit breaker type VA-2 and VAS-2

Offers an additional protection against negative effects from an internal arc.
– extinguishes the arc in less then 50 ms
– for use in air insulated switchgear
– patented design

Includes:
– earthing knife on support for mounting on VA(S)-2
– fixed contacts for earthing knife to be mounted on VA(S)-2
– drive mechanism
– fastening accessories

IEC tested at KEMA according IEC 60298 Annex AA.

Test cycle:
1. rated power frequency withstand voltage 1 min: 38 kV
2. rated lightning impulse withstand voltage: 95 kV (15x + en 15x -)
3. internal arc withstand test 14/16/20 kA 1 s: alle 6 criteria voldaan
4. rated power frequency withstand voltage 1 min: 50 kV

SV250002 – Arc Killer SV-25 Mechanism D

SV-25 Arc Killer
for use in medium voltage protection cubicle with vacuum circuit breaker type DF-D

Offers an additional protection against negative effects from an internal arc.
– extinguishes the arc in less then 50 ms
– for use in air insulated switchgear
– patented design

Includes:
– drive mechanism

IEC tested at KEMA according IEC 60298 Annex AA.

Test cycle:
1. rated power frequency withstand voltage 1 min: 38 kV
2. rated lightning impulse withstand voltage: 95 kV (15x + en 15x -)
3. internal arc withstand test 14/16/20 kA 1 s: alle 6 criteria voldaan
4. rated power frequency withstand voltage 1 min: 50 kV

SV250045 – Earthing switch for SV-25 A

Earthing switch for SV-25 A

SV500000 – SV-50 Left – Arc Killer

The SV-50 Arc Killer is a patented innovation that extinguishes an internal arc in fewer than 50 ms.

This SV-50 Arc Killer is suitable for Gas Insulated Switchgear.

KEMA type tested according to IEC 60298 Appendix AA.

Test cycle :
Power frequency withstand test 1 min.: 38 kV.

BIL : 95 kV (15 x + and 15 x -).

Internal arc test 14/16/20 kA 1 s – All 6 criteria met.

Power frequency withstand test 1 min.: 50 kV.

The Arc Killer ‘s lightning-fast respons quarantees not only complete operator safety, it also prevents damage to the installation room. What’s more, it ensures that your production is quickly up and running again in case of any potential damage: only the affected RMU will need to be replaced instead of an entire installation.

Our SV-50 Arc Killer activates under 50 ms, six times faster than the blink of a human eye. This lightning-fast response prevents any serious damage from occurring to the operator, the room and the building.

Time is energy and by killing an arc quickly, large build-ups of energy are short circuited, which results in complete safety for the operator and the installation room.

Our SV-50 Arc Killer is a patented solution. After years of R&D, Mevoco is proud to provide a patented solution. The arc-killer represents Mevoco’s continued quest for quality, reliability and safety.

SV500006 – SV-50 Right – Arc Killer

SV-50 Right – Arc Killer

Extinguishes an arc in fewer than 50 ms.

The SV-50 Arc Killer is a patented innovation that extinguishes an internal arc in fewer than 50 ms.
The Arc Killer ‘s lightning-fast respons quarantees not only complete operator safety, it also prevents damage to the installation room. What’s more, it ensures that your production is quickly up and running again in case of any potential damage: only the affected RMU will need to be replaced instead of an entire installation.

Our SV-50 Arc Killer activates under 50 ms, six times faster than the blink of a human eye. This lightning-fast response prevents any serious damage from occurring to the operator, the room and the building.

Time is energy and by killing an arc quickly, large build-ups of energy are short circuited, which results in complete safety for the operator and the installation room.

Our SV-50 Arc Killer is a patented solution. After years of R&D, Mevoco is proud to provide a patented solution. The arc-killer represents Mevoco’s continued quest for quality, reliability and safety.

DF045601- Set of handles for Arc Killer VA-2

Operating handles for Arc Killer on VA-2

For operating the mechanism of an Arc Killer.

Includes:
– 1 lever for charging
– 1 lever for discharging